CD Automation Soft Starter
CD Automation Soft Starters are designed to drive three phase, three wire, squirrel cage induction motors, providing a reliable, efficient and energy saving solution for the industrial use of electric motors.
Three different family’s are available:
- STB: Basic model (3 wire)
- STO: Medium performance model (3 wire)
- STE: Enhanced soft start performance model (3 & 6 wire)
Soft Starter Selection
- Start from application table on the right Example (below in case you are looking this page with a mobile device): Agitator 50A the suggested start current is 4 times FLC (full load current 50A)
- Select model from table at the bottom page
- Go on column HEAVY (4) and nominal current of your motor must be equal or less than the value (In our example is 55A)
- If selected model is STB your soft starter is STB075
- If you want to receive Soft Starter already configured follow the code below.
APPLICATION |
3 In |
3,5 In |
4 In |
4,5 In |
AGITATOR |
|
|||
ATOMIZER |
|
|||
BANDSAW |
|
|||
BOTTLE WASHER |
|
|||
CENTRIFUGAL PUMP |
|
|||
CENTRIFUGE |
|
|||
CHIPPER |
|
|||
CIRCULAR SAW |
|
|||
CONVEYOR BELT |
|
|||
CONVEYOR SCREW |
|
|||
CRANE TRANSLATOR |
|
|||
CRUSHER CONE |
|
|||
CRUSHER JAW |
|
|||
CRUSHER ROTARY |
|
|||
CRUSHER VERTICAL IMPACT |
|
|||
DEBARKER |
|
|||
DRYER |
|
|||
DUST COLLECTOR |
|
|||
EDGER |
|
|||
ELEVATOR |
|
|||
FAN AXIAL CLAMPED |
|
|||
FAN AXIAL UNCLAMPED |
|
|||
FAN CENTRIFUGAL CLAMPED |
|
|||
FAN CENTRIFUGAL UNDAMPED |
|
|||
FAN HIGH PRESSURE |
|
|||
GRINDER |
|
|||
HYDRAULIC POWER PACK |
|
|||
LOADED PISTON COMPRESSOR |
|
|||
MILL |
|
|||
MILL BALL |
|
|||
MILL HAMMER |
|
|||
MIL ROLLER |
|
|||
MIXER |
|
|||
MONORAILS |
|
|||
PALLETISER |
|
|||
PLANER |
|
|||
POSITIVE DISPLACEMENT PUMP |
|
|||
PRESS |
|
|||
PUMPS BORE |
|
|||
REPULPER |
|
|||
ROLLER CONVERYOR |
|
|||
ROTARY TABLE |
|
|||
SANDER |
|
|||
SCREW COMPRESSOR |
|
|||
SCREW CONVEYOR |
|
|||
SEPARATOR |
|
|||
SHREDDER |
|
|||
SLICER |
|
|||
SLURRY PUMP |
|
|||
TUMBLER |
|
|||
UNLOADED PISTON COMPRESSOR |
|
|||
HYDRAULIC PUMP |
|
SERVICE |
LIGHT |
MEDIUM |
HEAVY |
SEVERE |
|
Start Current (Multliple of FLC*) |
3 |
3,5 |
4 |
4,5 |
|
AC53b 3,0 -10:350<1000m |
AC53b 3,5 -15:345<1000m |
AC53b 4,0 -20:340<1000m |
AC53b 4,5 -30:340<1000m |
||
MODEL |
Rating at 40° C for 3xFLC |
Rating at 40° C Amps |
Rating at 40° C Amps |
Rating at 40° C Amps |
|
STB |
006 |
6A |
5A |
4A |
3A |
STB |
012 |
12A |
11A |
9A |
7A |
STB |
022 |
22A |
20A |
17A |
13A |
STB |
032 |
32A |
29A |
25A |
19A |
STB – STO – STE |
043 |
43A |
40A |
35A |
29A |
STB – STO – STE |
050 |
50A |
44A |
38A |
30A |
STB – STO – STE |
060 |
60A |
55A |
48A |
37A |
AC53b 3,0 -6:590<1000m |
AC53b 3,5 -15:585<1000m |
AC53b 4,0 -20:580<1000m |
AC53b 4,5 -30:570<1000m |
||
STB – STO – STE |
075 |
75A |
65A |
55A |
47A |
STB – STO – STE |
100 |
100A |
88A |
75A |
61A |
STB – STO – STE |
140 |
140A |
123A |
107A |
90A |
STB – STO – STE |
170 |
170A |
145A |
122A |
97A |
STB – STO – STE |
200 |
200A |
190A |
160A |
135A |
- Click to see the comparision between our units
SOFT STARTERS MAIN FEATURES
STB
STO
STE
GENERAL
Current range
6:200A
>32:200A
>32:200A
3 wire motor connection
Internal bypass St. from 6 to 200A
MAIN SUPPLY VOLTAGE
Supply voltage 3x200V; 3x440V Max (+10 : -15%) ac
Supply voltage 3x200V; 3x575V Max (+10 : -15%) (just for >32A)
Auxiliary voltage 110-240V (+10 : -15%) ac (just for >32A)
Auxiliary voltage 380-440V (+10 : -15%) ac (just for >32A)
Auxiliary voltage 24V ac/dc (+20 : -20%) ac (just for >32A)
Voltage frequency 45 to 66 Hz
DIGITAL INPUTS
Start/stop optoisolated input + 24V dc start with Dip 4 off (≤32A)
Start with power up with Dip 4 on (≤32A)
Start optoisolated input + 24V dc
Stop optoisolated input + 24V dc
Configurable digital input 1
Configurable digital input 2
CONTROL
Ramp up 0 to 15 sec adjustable
Ramp down 0 to 15 sec adjustable
Initial torque 0 to 80%
Current limit >32A
Motor full load current >32A
Overload relay >32A
Digital in/out >32A
Phase sequence enable >32A
Exceded max start time >32A
LED STATUS ALARM INDICATION
Run green led slow blinking ready to start
Run green led fast blinking ramp active
Run green led on end of ramp
Alarm red led off no alarm
PW green on power supply available
PW green on power supply not available
KEYPAD
Rotary switch
Colour touch panel with alarm message in different language
Read out of voltage, current, power etc
Logging and trend
COMMUNICATION
Modbus RTU Std
USB device Std
Modbus TCP (option)
Profibus DP (option)
Profinet (option)
Devicenet (option)
ENVIRONMENTAL
Protection IP20
Current sizing as in TAB for 40°C for temperature over see derating
Operating temperature -10 to 60°C max
Humidity 5% to 95% relative humidity
Conformal coating (option)
RELAY OUTPUT
2 Relay output free voltage contact (500mA, 125 Vac)
(1)
FUNCTIONALITY
STB
STO
STE
START / STOP
Ramp up voltage
Ramp up current
Ramp down
Stop by coasting
CONTOL MODE
Internal bypass relay up to 200A
Current limit facility
Torque control
Constant current control
kick start 80% 100 msec
kick start 80% 200 msec
kick start 80% 300 msec
kick start 80% adjustable msec
PROTECTION
Start time out of limit
Phase loss
(1)
Motor overload
Phase sequence
Unbalanced current
Power circuit failure
Thyristor in short circuit
Supply frequency out of limits
Istantaneous peak current
Bypass overload
Overvoltage
Overcurrent
Undercurrent protection (pump)
Overtemperature on heatsink
Overload relay and curve selection
PTC motor termistor
Communication failure
Communication
Modbus RTU Std
Modbus TCP (option)
Profibus DP (option)
Profinet (option)
USB device Std
Devicenet (option)
SOFTWARE APPLICATIONS
Pump application
STB Basic Soft Starter
- STB family has 3 adjustaments: - Initial start voltage -Start ramp time -Soft stop ramp time
- Kickstart 100 to 300 msec can be configured by DIP switch
- DIN rail or fixing hole mounting: from 6 to 32A
- Fixing hole mounting from 42 to 200A
STO Mid Performance Soft Starter
- STO family rotary adjustaments on front unit: - Initial start voltage - Start ramp time - Stop ramp time
- Kickstart 100, 200 or 300 msec can be configured by DIP switch
- Internal electronic overload relay
- Hole mounting from 42 to 200A fixing
- Modbus RTU standard
- USB device standard
- Modbus TCP option
- Profibus DP option
- Profinet option
- Devicenet option
STE Enhanced Performance Soft Starter
- Color touch panel for an easy human interface
- Special vector control
- Message and information, front display panel in different languages
- Voltage Current and Power available
- Trend of electrical variable
- Two configurable digital input
- Two configurable digital Output
- Most popular FieldBus*: ModBus RTU standard USB port standard ModBus TCP available as option Profibus DP available as option Profinet available as option Devicenet available as option Ethercat available as option Ethernet IP available as option Powerlink available as option *Logos and trademarks shown above are of their respective owners